A Burned-Out Bulb and a Missing Strap Crashed New York's Air Traffic Control

One Manhattan power room took down FAA air traffic control in 1991

A Burned-Out Bulb and a Missing Strap Crashed New York's Air Traffic Control

On September 17, 1991, a routine generator transfer at AT&T's windowless 33 Thomas Street hub tripped the rectifiers in its 20th-floor power room. Backup batteries masked the fault for over six hours, but a burned-out indicator lamp, a missing 25-inch jumper strap, a clamped alarm bell, and an unstaffed watch handoff kept anyone from noticing. When the batteries died at 4:40 p.m., radar and radio links to New York TRACON and three airports failed, disrupting 1,174 flights.

The alarm was clamped so that it was ringing lightly, but not loud enough to be audible.
  1. crmd

    > Because the alarm wire carried current only during a fault, an open 25-inch strap produced the same electrical state at the receiving end as a healthy power plant.

    I’m a building automation and controls tech in Manhattan, and for this exact reason digital feedback points and alarms are always normally-closed, and analog points are 4-20mA. This allows differentiation between nominal zero values and a fault in the loop.

    Disasters like this are what our best practices are borne from.

  2. mandevil

    20 years ago some friends and I were walking by 33 Thomas St and discussed how that must be the building that they imprison Magneto in. Weird looking building.

  3. gfat

    The overall site has a cozy feel to it. Well done